Rec No. | Date | Loc From | Title | Loc To | Notes |
4799 |
2020-09-16 |
Vaira Battery Bank SoilCO2 |
Maintenance |
Vaira Battery Bank SoilCO2 |
I checked the water in the soil co2 battery bank. The water levels were low exposing the plates but these batteries didn’t take that much water – about a gallon to fill all of them. |
3478 |
2018-06-05 |
Twitchell Alfalfa |
Replaced |
Vaira |
The battery bank from Twitchell Alfalfa was installed to replace the original batteries here that had a catastrophic failure |
4644 |
2012-03-21 |
Lab none |
Installed |
Vaira none |
I installed new batteries (borrowed from DWR) for the new soil co2 system. The original batteries were killed because they were wired for 24V and the solar for 12V. |
4643 |
2012-03-19 |
Vaira |
Removed |
Lab none |
The four new batteries for the soil CO2 sensors were completely dead (~2V). The batteries were wired for 24V but the solar panels were wired for 12V. Batteries removed. |
4642 |
2012-02-16 |
Lab none |
Installed |
Vaira none |
Initial installation of the VR_soilco2 battery bank. Two pairs of deep cycle batteries were installed for a 24V system. However the solar panels were only wired as 12V and bled the batteries dry. |