Equipment and Calibration History

View Equipment |

View history entry 6423 for Fabricated BB-Fab sn: BB-WP

Date: 2023-09-19
From: West Pond - Battery Bank
To: West Pond - Battery Bank
Title: Maintenance
Notes: I disconnected the batteries and tested them with the load tester. The first three from the west tested okay but the last one on the east tested weak. These are wired in 24V pairs and the one paired with the weak battery had a bunch of corrosion on its positive terminal. So I disconnected these two and left the system running on a single pair. I also check the water levels and added a little water to a couple of cells that were low.
Entered by: Joe Verfaillie
Field notes