Equipment and Calibration History

View Equipment |

View history entry 6403 for Fabricated BB-Fab sn: BB-WP

Date: 2023-01-18
From: West Pond - Battery Bank
To: West Pond - Battery Bank
Title: Tested
Notes: The batteries looked clean and in good condition. After disconnecting and isolating them, two of the six tested bad: 4 and 5 counting from the west. The system is wired in pairs for 24V and the two bad batteries were members of adjacent pairs. They were also the only ones that had cells that were low on water. Joe removed the two bad batteries then reconnected the remaining four.
Entered by: Joe Verfaillie