2023-09-19 |
From: |
West Pond - Battery Bank |
To: |
West Pond - Battery Bank |
Title: |
Maintenance |
Notes: |
I disconnected the batteries and tested them with the load tester. The first three from the west tested okay but the last one on the east tested weak. These are wired in 24V pairs and the one paired with the weak battery had a bunch of corrosion on its positive terminal. So I disconnected these two and left the system running on a single pair. I also check the water levels and added a little water to a couple of cells that were low. |